Feb-21
Sample LocationTotal ColiformsFecal ColiformsHeterotrophic Plate CountRemarks
(PNSDW* Standard <1.1)(PNSDW* Standard <1.1)(PNSDW* Standard <500CFUa/ml)
Brgy. Rajal Sur<1.1<1.1<1 CFUb/mlPassed
Brgy. Liwayway (Purok 4)<1.1<1.1320 CFUb/mlPassed
Brgy. Malacañang (Purok 4)<1.1<1.1<1 CFUb/mlPassed
Brgy. Malacañang (Purok 2)<1.1<1.12 CFUb/mlPassed
Brgy. Malacañang MGL<1.1<1.1<1 CFUb/mlPassed
Brgy. Mapalad (Purok 4)<1.1<1.13 CFUb/mlPassed
Brgy. Mapalad (Purok 4)<1.1<1.12 CFUb/mlPassed
Brgy. Mapalad Pump Station<1.1<1.1<1 CFUb/mlPassed
Brgy. Soledad Pump Station<1.1<1.115 CFUb/mlPassed
Brgy. Soledad Pump Station<1.1<1.128 CFUb/mlPassed
Brgy. Rizal Pump Station<1.1<1.12 CFUb/mlPassed
Brgy. Del Pilar<1.1<1.125 CFUb/mlPassed
Brgy. Gomez Pump Station<1.1<1.12 CFUb/mlPassed
Brgy. La Fuente Pump Station<1.1<1.11 CFUb/mlPassed
Brgy. Sap-sap Pump Station<1.1<1.1<1 CFUb/mlPassed
Brgy. Rajal Pump Station<1.1<1.15 CFUb/mlPassed
Sta. Rosa Homes Pump Station<1.1<1.1110 CFUb/mlPassed

Notes:

*Philippine National Standards for Drinking Water
aPhilippine National Standards for Drinking Water
bColony-forming Units