Sample No.: P00105229-01
Sample ID: RAJAL PUMPING STATION
Date sampled: 07-14-20 06:30
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C7.56.5-8.5Electrometric Method7/14/2020MDLL1123
Color**3Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**0.15NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**293mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**0.3mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-01<<<

Sample No.: P00105229-02
Sample ID: CONSUMER TAP
Date sampled: 07-14-20 06:52
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C7.16.5-8.5Electrometric Method7/14/2020MDLL1123
Color**3Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**0.25NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-02<<<

Sample No.: P00105229-03
Sample ID: OMICO STATION
Date sampled: 07-14-20 08:00
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C7.66.5-8.5Electrometric Method7/14/2020MDLL1123
Color**3Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**0.2NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**254mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**0.2mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-03<<<

Sample No.: P00105229-04
Sample ID: LIWAYWAY PUMPING STATION
Date sampled: 07-14-20 07:45
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C7.96.5-8.5Electrometric Method7/14/2020MDLL1123
Color**3Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**0.75NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**226mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**0.7mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-04<<<

Sample No.: P00105229-05
Sample ID: MAPALAD PUMPING STATION
Date sampled: 07-14-20 06:10
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C6.96.5-8.5Electrometric Method7/14/2020MDLL1123
Color**3Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**0.55000000000000004NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**115mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**6.5mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-05<<<

Sample No.: P00105229-06
Sample ID: SAP-SAP PUMPING STATION
Date sampled: 07-14-20 09:36
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C7.46.5-8.5Electrometric Method7/14/2020MDLL1123
Color**3Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**0.35NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**294mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**0.3mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-06<<<

Sample No.: P00105229-07
Sample ID: RIZAL PUMPING STATION
Date sampled: 07-14-2010:26
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C7.46.5-8.5Electrometric Method7/14/2020MDLL1123
Color**8Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**1.9NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**347mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**0.3mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-07<<<

Sample No.: P00105229-08
Sample ID: SAN GREGORIO PUMPING STATION
Date sampled: 07-14-20 08:44
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C7.76.5-8.5Electrometric Method7/14/2020MDLL1123
Color**5Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**1.8NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**238mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**0.3mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-08<<<

Sample No.: P00105229-09
Sample ID:  SOLEDAD PUMPING STATION
Date sampled: 07-14-20 10:00
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C86.5-8.5Electrometric Method7/14/2020MDLL1123
Color**3Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**0.25NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**236mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**0.6mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-09<<<

Sample No.: P00105229-10
Sample ID: GOMEZ PUMPING STATION
Date sampled: : 07-14-20 09:40
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C86.5-8.5Electrometric Method7/14/2020MDLL1123
Color**3Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**0.25NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**236mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**0.3mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-10<<<

Sample No.: P00105229-11
Sample ID: LA FUENTE PUMPING STATION
Date sampled: 07-14-20 08:16
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.008mg/L0.01ICP – OES7/17/2020PPG1123
Cadmium<0.001mg/L0.003ICP – OES7/17/2020PPG1123
Lead<0.005mg/L0.01ICP – OES7/17/2020PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C86.5-8.5Electrometric Method7/14/2020MDLL1123
Color**3Apparent CU10Visual Comparison7/15/2020MPT1123
Turbidity**0.2NTU5Nephelometry (Turbidimeter)7/14/2020ATDR1123
Total Dissolved Solids**247mg/L600Gravimetry (SM2540 C)7/15/2020ATDR1123
Nitrate**0.3mg/L50Cadmium Reduction Method7/15/2020NGCM1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD7/14/2020ATDR1123
>>>end of result set for Sample No.:P00105229-11<<<

N/S = Not Supplied
**PAB approved parameter/s
Results are reported “as received basis”.
ICP – OES = Inductively Coupled Plasma – Optical Emission Spectroscopy
Standard Methods for the Examination of Water and Wastewater, APHA, AWWA, WEF 23rd Edition.
Test Methods for Evaluating Solid Wastes, Vol 1A, USEPA, Third Edition
*Regulatory Limit Reference
1123Philippine National Standards for Drinking Water, 2017