Sample No.: P00126130-01
Sample ID: Del Pilar
Date sampled: 05-30-2022 09:40
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01 ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH**, Laboratory @ 25.0°C8.26.5-8.5Electrometric Method6/14/2021MLJ1123
Color**5Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity**0.25NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Chlorine**, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126130-01<<<

Sample No.: P00126130-02
Sample ID: San Gregorio Pump Station
Date sampled: 05-30-2022 09:29
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.96.5-8.5Electrometric Method6/14/2021MLJ1123
Color3Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.55NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids241mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126130-02<<<

Sample No.: P00126130-03
Sample ID: Gomez Pump Station
Date sampled: 05-30-2022 09:06
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C8.26.5-8.5Electrometric Method6/14/2021MLJ1123
Color3Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.4NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids239mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>>end of result set for Sample No.:P00126130-03<<<

Sample No.: P00126130-04
Sample ID: La Fuente
Date sampled: 05-30-2022 08:27
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C86.5-8.5Electrometric Method6/14/2021MLJ1123
Color8Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity5.2NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids243mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126130-04<<<

Sample No.: P00126130-05
Sample ID: Sap-sap Pump Station
Date sampled: 05-30-2022 07:12
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.46.5-8.5Electrometric Method6/14/2021MLJ1123
Color3Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.8NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids313mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126130-05<<<

Sample No.: P00126130-06
Sample ID: Sta. Rosa Homes Pump Station
Date sampled: 05-30-2022 07:54
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.86.5-8.5Electrometric Method6/14/2021MLJ1123
Color3Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.55NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids270mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126130-06<<<

Sample No.: P00126130-07
Sample ID: Soledad Pump Station
Date sampled: 05-30-2022 09:52
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.56.5-8.5Electrometric Method6/14/2021MLJ1123
Color3Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.2NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids397mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126130-07<<<

Sample No.: P00126130-08
Sample ID: Rajal
Date sampled: 05-30-2022 06:52
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.76.5-8.5Electrometric Method6/14/2021MLJ1123
Color3Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.45NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids308mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126130-08<<<

Sample No.: P00126130-09
Sample ID: Rizal
Date sampled: 05-30-2022 08:59
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.76.5-8.5Electrometric Method6/14/2021MLJ1123
Color5Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.5NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-07<<<

Sample No.: P00126134-01
Sample ID: Liwayway Pump Station
Date sampled: 05-30-2022 06:30
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C86.5-8.5Electrometric Method6/14/2021MLJ1123
Color8Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.45NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids241mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-01<<<

Sample No.: P00126134-02
Sample ID: Mapalad Pump Station
Date sampled: 05-30-2022 07:15
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.26.5-8.5Electrometric Method6/14/2021MLJ1123
Color3Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.05NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids124mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate0.06mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-02<<<

Sample No.: P00126134-03
Sample ID: Trinidad Pump Station
Date sampled: 05-30-2022 07:40
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.46.5-8.5Electrometric Method6/14/2021MLJ1123
Color3Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.15NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids226mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-03<<<

Sample No.: P00126134-04
Sample ID: Malacañang Pump Station
Date sampled: 05-30-2022 08:38
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.16.5-8.5Electrometric Method6/14/2021MLJ1123
Color3Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.35NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids240mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate0.5mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-04<<<

Sample No.: P00126134-05
Sample ID: Mapalad Brgy. Hall Pump Station
Date sampled: 05-30-2022 09:15
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.76.5-8.5Electrometric Method6/14/2021MLJ1123
Color5Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.6NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids156mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-05<<<

Sample No.: P00126134-06
Sample ID: Bulk Water
Date sampled: 05-30-2022 09:40
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.76.5-8.5Electrometric Method6/14/2021MLJ1123
Color5Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.65NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids164mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-06<<<

Sample No.: P00126134-07
Sample ID: Rizal
Date sampled: 05-30-2022 09:15
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.76.5-8.5Electrometric Method6/14/2021MLJ1123
Color5Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.5NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-07<<<

Sample No.: P00126134-08
Sample ID: Upland Soledad
Date sampled: 05-30-2022 10:01
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.76.5-8.5Electrometric Method6/14/2021MLJ1123
Color5Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.65NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids162mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-08<<<

Sample No.: P00126134-09
Sample ID: Malacañang Purok 7
Date sampled: 05-30-2022 08:15
Matrix: Drinking Water

TEST DESCRIPTIONRESULTS UNITSREG LIMITTEST METHODSDATE ANALYZED BYRef*
-Metals-
Arsenic<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Cadmium<0.001mg/L0.003ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
Lead<0.005mg/L0.01ICP – OES (SMEWIN 312013 EPA 601013)6/17/2021PPG1123
-Wet Chemistry-
pH, Laboratory @ 25.0°C7.76.5-8.5Electrometric Method6/14/2021MLJ1123
Color5Apparent CU10Visual Comparison6/14/2021MPT1123
Turbidity0.55NTU5Nephelometry (Turbidimeter)6/14/2021ADP1123
Total Dissolved Solids160mg/L600Gravimetry (SM2540 C)6/16/2021ADP1123
Nitrate<0.006mg/L50Cadmium Reduction Method6/16/2021ANBB1123
Chlorine, Residual<0.02mg/L0.3 – 1.5Colorimetry – DPD6/14/2021ADP1123
>>>end of result set for Sample No.:P00126134-09<<<

Results are reported “as received basis”.
ICP – OES = Inductively Coupled Plasma – Optical Emission Spectroscopy
Standard Methods for the Examination of Water and Wastewater, APHA, AWWA, WEF 23rd Edition.
Test Methods for Evaluating Solid Wastes, Vol 1A, USEPA, Third Edition
*Regulatory Limit Reference
1123Philippine National Standards for Drinking Water, 2017